Wire Gauge Calculator

Size the DC cable between your battery bank and inverter. Enter the system voltage, inverter load, and one-way run length — the tool works out the minimum copper gauge that keeps voltage drop and heating within safe limits.
Inputs
Tighter (1%) 3.0% Looser (10%)
Calculation covers round-trip conductor length (out and back) using standard copper/aluminum resistivity, then checks the result against typical chassis-wiring ampacity so the cable can also carry the current without overheating. For a permanent installation, confirm the final size against your local electrical code or a qualified electrician.
Recommended gauge
AWG 2
Within limits
Circuit readout
Current draw
Voltage drop
Drop percent
Required ampacity
Conductor cross-section
Illustrative scale drawing of the recommended conductor, across, shown against the reference ring for AWG 20 (thinnest common gauge). Strand pattern is representative, not a manufacturer spec.
Reference table — AWG sizes used in this calculation
AWGArea (cmil)DiameterTypical ampacity
Ampacity figures reflect common chassis/marine-style continuous-duty wire ratings, not a specific national electrical code table. Voltage-drop math uses K = 12.9 Ω·cmil/ft for copper and K = 21.2 Ω·cmil/ft for aluminum at room temperature. Recommendations include a 1.25× continuous-load margin on ampacity. Always size overcurrent protection (fuse/breaker) to the wire's ampacity, not just to the load.