frequency speed and voltage of inverter

 

set only  to fine adjust v/f for the output range when using flux vector control of frequency speed and voltage of inverter .normally this setting range and factory setting will be cut by 50%  for the inverter of 200v class . to set the constant e 1-0 4 ~e 1-10 when e 1-0 3 =”f” the setting except “f” is only for reference . when v/f characteristics is straight line please set the value of e 1-0 7 same as the value  of  e 1-0 9 now the constant e 1- 0 8 is invalid.
 



 

for the inverter of 200 v class, frequency speed and voltage of inverter the setting range and factory setting will be cut by 50% . if  v/f characteristic  needs to be set as a straight line please set e 1 -0 7 ,s value is same to be e 1 -0 9 in this case e 1- 0 8,s setting will be taken as disabled . please set the 4 frequencies according to below. e 1- 0 4 (f max ) >e 1- 0 6 (f a > e 1- 0 7 (f b) >e 1-0 9 (f main).

input voltage setting.
to set the input frequency speed with voltage of inverter in unit of v.
1 for 200 v class inverter, the setting range and factory setting will be cut by 50% .
note:
the voltage settings shown in parentheses are the values for the 400 v class. the setting is used as the reference value for functions such as protection functions. set input voltage (e 1- 0 1)according to the input voltage.

motor selection.frequency speed and voltage of inverter
motor selection.motor overheating protection
0:standard motor (general purpose motor )
1: special motor (inverter exclusive motor)
2:special motor (vector motor )
set it is as motor,s protection reference.

frequency speed and voltage of inverter, it is used to  set the delay  time from inputting the multi function input speed/torque control change (off-on or on-off)until the actual control is changed in unit of  MRS.

 



 

NOTE:
frequency speed and voltage of inverter, the timer setting is effective only when 71 (speed/torque control change)has been set in one of the multi function inputs (h 1-0 1 to h 1-0 6). this setting specifies the delay (0 to 1,000  m s )between a change in the multi function input (on, off or off  on )and the corresponding change in the control mode . during the timer delay the value of the 3 analog inputs will retain the values they had when the on/off status of speed/ torque control switching signal was changed . use this delay to make any preparations for the change in the control mode.

it is used to set the speed limit bias in unit of 100 % with max , output frequency take as 100%.

setting range is 0~120
factory setting is 10
NOTE:
the speed limit bias can be used to adjust the margins of the speed limit , when the speed limit bias is used , it is possible to set the same speed limit value in both the forward and reverse directions.
set the speed limit bias as a percentage of the maximum output frequency . (the max .frequency is 100%), for example  the following settings establish speed limits of 50% of the maximum output frequency in both the forward and reverse directions. speed limit bias setting  50%(d 5-0 5=50).

when a forward speed limit and a speed limit bias have been set the speed range of the torque control is from the – speed limit bias setting to the speed limit setting + speed limit bias setting.in effect the speed limit range is extended by the speed limit bias in frequency speed and voltage of inverter  the forward and reverse directions.

solar inverter

 



 

10 thoughts on “frequency speed and voltage of inverter”

  1. Your blog is a constant source of inspiration for me. Your passion for your subject matter shines through in every post, and it’s clear that you genuinely care about making a positive impact on your readers.

    Reply

Leave a Comment